03 · Commercial Heating

Why Is My Commercial Heating System Losing Pressure?

  • By Flair Facilities Ltd engineering team
  • Published
  • Updated
  • Read 6 min
Quick answer

A sealed commercial heating system loses pressure because water is leaving it, or because the expansion vessel can no longer absorb thermal expansion. The usual causes are leaks at joints, valves and emitters; a pressure relief valve discharging; an expansion vessel that has lost its pre-charge; or a pressurisation unit that is not topping up. A rising number of top-ups recorded by the pressurisation unit is the most reliable early warning.

How does pressure work in a sealed heating system?

Commercial LTHW systems are usually sealed: filled with treated water, pressurised and closed to atmosphere. Three components maintain stable pressure:

  • The pressurisation unit, which adds water from a break tank when pressure falls below its set point
  • One or more expansion vessels, where a gas cushion behind a membrane absorbs the extra volume as water heats
  • The pressure relief valve, a safety device that discharges water if pressure gets too high

When these are working, pressure moves within a narrow band between cold and hot conditions. When any of them fails, or water escapes, pressure drifts and boilers trip on low or high pressure.

Common symptoms of pressure loss

  • Boilers showing low water pressure faults or locking out
  • The pressurisation unit running frequently or alarming on low pressure
  • Pressure falling overnight when the system is cold
  • Large pressure swings between morning start-up and full load
  • Water around relief valve discharge points, tundishes or drains
  • Damp patches, staining or corrosion near pipework or emitters

What causes a commercial heating system to lose pressure?

CauseHow it presentsTypical check
Leak at joints, valves or emittersSteady loss, regular top-upsVisual survey of plant room, risers, emitters; monitor top-up volume
Hidden leak in voids or undergroundSteady loss with nothing visibleIsolate circuits in turn to locate; thermal imaging
Relief valve dischargingWater at discharge points when hotCheck vessel charge and fill pressure
Expansion vessel lost pre-charge or failed membraneLarge pressure swings, then relief valve dischargeEngineer checks pre-charge with system drained down on that vessel
Pressurisation unit faultPressure not restored, low-pressure alarmCheck break tank level, pump operation and settings
Automatic air vents leakingSlow loss, staining at high levelInspect vents, especially after air problems
Heat exchanger leak into another circuitPressure lost from one circuit while another gainsCompare pressures across connected circuits

The expansion vessel chain reaction

Expansion vessel failure is a common root cause because its effects appear elsewhere. When the gas cushion is lost, the vessel cannot absorb expansion. As the system heats, pressure climbs until the relief valve lifts and dumps water. As it cools, pressure falls below the pressurisation set point and the unit refills. Each cycle loses water through the relief valve and adds fresh water, accelerating corrosion. Read more in pressurisation unit faults.

Diagnostic considerations

  1. Record pressure at the same time each day for a week, cold and hot.
  2. Note pressurisation unit top-ups: many units log run hours or starts. A water meter on the fill line gives a direct measurement.
  3. Look for wet tundishes and drains near relief valves.
  4. Walk the system: plant room, risers, ceiling voids where accessible, and any external or underground runs.
  5. Isolate circuits one at a time (engineer-led) to see which section is losing water.
  6. Check water treatment results for rising iron, indicating active corrosion.

Safety: Heating systems contain hot water under pressure. Do not open vessel valves, relief valves or drain points, and do not attempt to isolate circuits on a live system unless you are competent to do so. Discharging relief valves can release scalding water.

When should you involve a qualified engineer?

Call an engineer if pressure will not hold, if the pressurisation unit is running more than usual, if relief valves are discharging, if you suspect a hidden leak, or if boilers are tripping on pressure. Expansion vessel checks and recharging, relief valve replacement and leak location on live systems are engineer tasks.

Practical recommendations for facilities managers

  • Record the design cold fill pressure and normal operating range in the plant room log
  • Log pressure daily during the heating season
  • Ask for pressurisation unit top-up data at each PPM visit
  • Include expansion vessel pre-charge checks in annual maintenance
  • Act on water treatment reports showing rising corrosion indicators
  • Investigate any increase in top-ups rather than relying on the unit to compensate

For the wider context, see the Commercial Heating guide and Water Pressure and Pumps.

flairfacilities.co.uk

More BMS expertise from Flair Facilities

Frequently asked questions

What pressure should a commercial heating system be at?

There is no single correct figure. It depends on the height of the system and the design. The cold fill pressure must exceed the static head at the boiler plus a margin, and is normally set at commissioning. Your log book or pressurisation unit should show the design setting.

Is it normal for heating pressure to rise when the system is hot?

A modest rise is normal as water expands. A large swing between cold and hot conditions usually indicates that the expansion vessel has lost its charge or is undersized.

Can a pressurisation unit hide a leak?

Yes. A healthy pressurisation unit will keep topping up a leaking system, masking the leak while drawing in fresh, oxygenated water that accelerates corrosion. Monitoring top-up frequency or using a water meter on the fill line reveals this.

Why does adding water cause corrosion?

Fresh mains water contains dissolved oxygen and minerals. Each top-up dilutes inhibitor and introduces oxygen, which corrodes steel components and produces sludge. That is why persistent top-ups should always be investigated.

UK technical references

Primary sources and industry guidance relevant to this topic. Always check you are working to the current edition.

  1. Pressure systems guidance — Health and Safety Executive
  2. BS EN 12828 and related heating system standards — BSI Knowledge
  3. BSRIA guidance on water treatment — BSRIA
  4. CIBSE knowledge portal — Chartered Institution of Building Services Engineers

This guide is general technical information for commercial property teams in the UK. It does not replace a site-specific assessment. Gas work must be carried out by a Gas Safe registered engineer, and work on electrical, pressurised or combustion equipment by competent, appropriately qualified people.