Commercial HVAC Systems: A Practical Guide to Faults and Maintenance

  • By Flair Facilities Ltd engineering team
  • Published
  • Updated
Quick answer

Commercial HVAC combines heating, ventilation and air conditioning to control temperature, fresh air and humidity. Most buildings use air handling units (AHUs) for fresh air, with fan coil units, VRF or chilled beams for room-level control. Comfort complaints are usually caused by controls, airflow or water-side problems rather than total equipment failure, so trend data and filter, damper and valve checks are the logical starting point.

What does a commercial HVAC system include?

Commercial HVAC is rarely a single piece of equipment. A typical UK office combines several systems:

  • Air handling units (AHUs) that deliver filtered, tempered fresh air, often with heat recovery
  • Terminal units such as fan coil units (FCUs), VAV boxes or chilled beams for local control
  • Cooling plant, which may be chillers with a chilled water circuit, or VRF/split systems using refrigerant directly
  • Heating coils fed from the LTHW heating system
  • Extract systems for toilets, kitchens and plant spaces
  • Controls, usually a BMS supervising local controllers

Understanding which system serves which area is the first step in any diagnosis. Many HVAC “faults” are interactions between them.

How do AHUs, fan coils and the BMS work together?

The AHU supplies a controlled quantity of fresh air at a set supply temperature. Fan coil units in each zone then trim the temperature using heating and cooling valves. The BMS coordinates time schedules, setpoints and interlocks: for example, preventing a fan coil heating while the AHU is supplying cool air, or enabling chillers only when there is cooling demand.

If the AHU supply temperature drifts, every fan coil compensates, and the building may simultaneously heat and cool. That is why supply air temperature and valve positions in trend logs are among the most useful diagnostic data you have.

Common commercial HVAC problems

SymptomLikely areas to investigate
Rooms too warm in summerChilled water temperature, cooling valve actuators, blocked coils, solar gain, controls deadbands
Rooms cold in winterHeating valve actuators, LTHW supply, fan speed, sensor location
Stuffy or stale airFresh air damper position, filter loading, fan faults, CO2 sensor calibration
Noise from ceilingsFan coil fan bearings, loose panels, high fan speed, air in coils
Water leaks from ceilingsBlocked fan coil condensate drains, failed condensate pumps, valve or coil leaks
High energy usePlant running out of hours, simultaneous heating and cooling, failed heat recovery

Detailed troubleshooting is covered in our AHU troubleshooting guide.

Safety: AHUs and fan coil units contain rotating fans, electrical supplies and, in some systems, pressurised refrigerant. Isolate and lock off equipment before any inspection panel is opened, and only allow F-gas certified engineers to work on refrigerant circuits.

Which compliance duties apply to commercial HVAC?

  • TM44 air conditioning inspections: required at least every five years for systems over 12 kW effective rated output in England and Wales.
  • F-gas leak checks: frequency depends on the refrigerant charge measured in tonnes of CO2 equivalent.
  • Ventilation: employers must provide sufficient fresh or purified air in workplaces under the Workplace Regulations.
  • Ductwork hygiene: kitchen extract ductwork in particular needs regular cleaning to manage fire risk, often specified by insurers.

What should facilities managers check between service visits?

  • BMS alarms for AHU fan, filter and frost protection status
  • Filter differential pressures against change thresholds
  • Supply air temperatures against setpoint across the day
  • Out-of-hours schedules and overrides
  • Reports of condensation, drips or staining on ceiling tiles
  • Occupant complaints logged by zone and time to spot patterns

When should you involve an HVAC engineer?

Bring in an engineer when the fault involves refrigerant, electrical components or fan drives, when leaks are present, when comfort complaints persist after basic control checks, or when you need compliance inspections. Sharing your complaint log and BMS trends means the engineer can focus on the right zone and the right system straight away.

flairfacilities.co.uk

More BMS expertise from Flair Facilities

Frequently asked questions

What is the difference between an AHU and a fan coil unit?

An air handling unit is central plant that filters, heats, cools and moves large volumes of air, usually including outside air, through ductwork. A fan coil unit is a smaller terminal unit serving a room or zone, recirculating room air across heating and cooling coils.

Do commercial air conditioning systems need inspecting by law?

In England and Wales, air conditioning systems with an effective rated output over 12 kW require an energy assessment by an accredited assessor at least every five years under the Energy Performance of Buildings Regulations (commonly called a TM44 inspection). Systems containing fluorinated gases also have leak-check duties under F-gas rules.

How often should AHU filters be changed?

It depends on the filter grade, the local air quality and run hours. Many buildings change on pressure drop rather than a fixed interval, using a differential pressure gauge or BMS alarm. Central London locations near busy roads often load filters faster.

Why does the office feel stuffy even though the air conditioning is on?

Stuffiness is usually a ventilation issue rather than a temperature one. Low fresh air rates, closed or stuck dampers, blocked filters, reduced fan speeds or CO2-based control faults can all leave rooms cool but under-ventilated.

UK technical references

Primary sources and industry guidance relevant to this topic. Always check you are working to the current edition.

  1. Energy Performance of Buildings (England and Wales) Regulations 2012 — legislation.gov.uk
  2. F gas in refrigeration, air conditioning and fire protection systems — GOV.UK
  3. Ventilation in the workplace — Health and Safety Executive
  4. Approved Document F: Ventilation — GOV.UK
  5. CIBSE knowledge portal — Chartered Institution of Building Services Engineers

This guide is general technical information for commercial property teams in the UK. It does not replace a site-specific assessment. Gas work must be carried out by a Gas Safe registered engineer, and work on electrical, pressurised or combustion equipment by competent, appropriately qualified people.