01 · BMS & Building Controls

BMS Temperature Sensor Faults: How to Spot and Diagnose Them

  • By Flair Facilities Ltd engineering team
  • Published
  • Updated
  • Read 6 min
Quick answer

A faulty BMS temperature sensor feeds wrong information into the control strategy, so plant does the wrong thing while appearing to work normally. Typical signs are values that are flat, erratic, implausible or out of step with nearby sensors, or zones that are uncomfortable while the BMS shows them at setpoint. Comparing readings against a calibrated hand-held thermometer and reviewing trend logs is usually enough to confirm the fault.

Why do sensor faults matter so much?

A BMS can only control what it can measure. If the outside air sensor reads 5°C too high, weather compensation sends cooler water to the building and every zone underheats. If a return air sensor in an AHU reads low, the unit heats when it should be cooling. The equipment works perfectly; it is simply responding to bad information. That is what makes sensor faults hard to spot.

Types of temperature sensor in a BMS

SensorTypical locationWhat it controls
Room sensorWall-mounted in occupied spacesFan coils, zone valves, VAV boxes
Duct sensorSupply, return or extract ductworkAHU heating and cooling coils
Immersion sensorIn a pocket in pipeworkBoiler sequencing, flow temperatures, calorifiers
Strap-on sensorClamped to pipeworkReturn temperatures, frost protection
Outside air sensorNorth-facing external wall, shadedWeather compensation, frost protection, optimum start

Common symptoms of a faulty sensor

  • A value that is flat-lined in trend logs while others vary
  • Erratic jumps or noise in the reading
  • Implausible values, such as -40°C in an office or 120°C on a heating return
  • A zone that occupants report as cold or hot while the BMS shows setpoint
  • Two sensors in the same space or pipe disagreeing by several degrees
  • Plant behaving oddly at certain times, such as heating starting very early

Potential causes

  • Drift: sensor elements gradually change characteristics over years
  • Poor location: sunlight, heat from IT equipment, draughts, or an outside sensor on a sunny wall
  • Wiring faults: loose terminals, damaged cables, corrosion, causing open or short circuits
  • Immersion pocket problems: sensor not fully inserted, no thermal paste, pocket in a dead leg
  • Strap-on sensors loose or uninsulated, reading ambient rather than pipe temperature
  • Configuration errors: wrong sensor type or scaling in the controller, or an offset left in place

Diagnostic considerations

  1. Look at trends first. Plot the suspect sensor alongside related points over several days. Healthy sensors move in plausible patterns.
  2. Compare with neighbours. Supply air should be close to the coil off temperature; return water should be below flow when heating.
  3. Check with a calibrated instrument at the sensor location and at occupant level.
  4. Inspect location and mounting for obvious influences such as sunlight or nearby heat sources.
  5. Check configuration: sensor type, offset and scaling in the controller. Offsets added in the past to “fix” complaints often mask the true fault.

Safety: Sensor wiring is often in panels with mains voltage nearby. Opening controllers, outstations or plant control panels should be left to competent controls engineers. Never change frost, high-limit or safety sensor settings to clear an alarm.

When should you involve a controls engineer?

When trends or spot checks suggest a fault, when wiring or controller inputs need testing, when sensors need replacing or recalibrating, or when control logic has been compensating for a bad reading and needs correcting. Ask for a record of any offsets applied, and for calibration results to be logged. Flair Facilities provides commercial BMS calibration and controls across London.

Practical recommendations for facilities managers

  • Keep a list of critical sensors that drive plant sequencing and prioritise their checks
  • Review trend logs monthly for flat-lined, noisy or implausible values
  • Record any offsets in the BMS and require justification for them
  • Check outside air sensor location and shading
  • Respond to repeated comfort complaints with a measured reading, not just a setpoint change

See the BMS and Building Controls guide for more on how sensors fit into the overall system, and our guide to BMS alarm management.

flairfacilities.co.uk

More BMS expertise from Flair Facilities

Frequently asked questions

How accurate should a BMS temperature sensor be?

Accuracy depends on the sensor type and application, but commercial room and duct sensors are typically expected to read within about ±0.5°C to ±1°C. Critical applications may require tighter tolerances. Check the specification in your O&M manual.

What does a reading of -50°C or 150°C mean?

Implausible extreme values usually mean an open or short circuit in the sensor or its wiring, rather than a real temperature. The controller is reading the electrical limit of its input.

Why is the room cold when the BMS says it is 21°C?

The sensor may have drifted, be located in a warm spot such as near equipment or in direct sun, or be reading a different space from the one occupants are in. Measure with a calibrated instrument at occupant level to compare.

How often should BMS sensors be calibrated?

Many PPM schedules check critical sensors annually. Outside air, supply air and return water sensors that drive plant sequencing are worth prioritising because errors affect the whole system.

UK technical references

Primary sources and industry guidance relevant to this topic. Always check you are working to the current edition.

  1. CIBSE Guide H: Building control systems (via the CIBSE knowledge portal) — Chartered Institution of Building Services Engineers
  2. Building Controls Industry Association — BCIA
  3. Temperature in the workplace — Health and Safety Executive

This guide is general technical information for commercial property teams in the UK. It does not replace a site-specific assessment. Gas work must be carried out by a Gas Safe registered engineer, and work on electrical, pressurised or combustion equipment by competent, appropriately qualified people.