BMS repair & fault finding · Greater London

BMS Repair and Fault Finding in London

When the building management system stops controlling the building properly, our controls engineers find the cause and fix it, on systems we installed and systems installed by others.

  • Comfort complaints with no obvious cause
  • Plant running when it should not, or not running at all
  • Outstations offline or front-end not responding
  • Alarms that will not clear
Trend log chart with a magnifying glass over a point where a valve is commanded fully open but supply temperature does not rise Original line chart. An orange line steps up to show the valve command at 100 per cent while the teal temperature line stays flat, indicating a faulty actuator or valve. TREND LOG · FAULT FINDING valve 100% · no temp rise Commanded vs actual: the gap points to the faulty device
In short

BMS repair means finding why the controls are not doing what they should and putting it right. Typical faults include failed or drifting sensors, seized valve and damper actuators, controller or I/O card failures, communication loss between outstations and the front-end, lost programmes and incorrect control logic. Good fault finding compares what the BMS commands with what the plant actually does, using trend data, before replacing anything.

What's included

BMS repair & fault finding: scope of work

  • 01

    Sensor faults

    Failed, drifting or poorly located sensors identified, recalibrated or replaced.

  • 02

    Actuators and valves

    Seized, slipping or failed valve and damper actuators diagnosed and repaired.

  • 03

    Controllers and I/O

    Failed outstations, I/O modules, power supplies and lost programmes restored.

  • 04

    Communications

    Network faults, addressing conflicts and lost links to the front-end traced and fixed.

  • 05

    Front-end and graphics

    Supervisor software faults, broken graphics and alarm routing problems resolved.

  • 06

    Control logic

    Incorrect sequences, unstable loops and conflicting heating and cooling corrected.

Common BMS faults we deal with

SymptomLikely areas
Zone too hot or too cold while BMS shows setpointSensor drift or location, wrong sensor scaling, offsets left in place
Valve commanded open, no change in temperatureSeized actuator, slipping linkage, air-locked coil, low water temperature
Plant running out of hoursSchedules, holiday calendars, overrides, failed relays
Outstation offlinePower supply, network cabling, addressing, controller failure
Plant cycling on and offLoop tuning, narrow differentials, sensor noise
Alarms flooding the front-endFailed sensors, poor limits, consequential alarms not suppressed

How we find the fault

Replacing parts until the problem goes away is expensive and often fails. We work through the control chain in order:

  1. Is the BMS reading the right conditions? Sensor values checked against calibrated instruments.
  2. Is it making the right decision? Control logic, setpoints, schedules and overrides reviewed.
  3. Is the command reaching the device? Outputs and wiring checked at the controller and in the field.
  4. Is the device responding? Actuators, relays and plant interfaces tested.
  5. Is the plant able to respond? If the controls are right, the fault is mechanical.

Trend data makes this much faster. See our guide to BMS temperature sensor faults for how faults show up in trend logs.

Safety: Fault finding is carried out with safe isolation on live panels. We never bypass frost, fire, high-limit or proving functions to restore service, because those protections exist to prevent plant damage and danger to occupants.

When repair is not the best answer

If controllers are obsolete and spares are scarce, or repeated faults trace back to an ageing system, repair may only buy time. We will say so and explain the options, including phased replacement through BMS upgrades and integration. To stop faults returning, a planned BMS maintenance programme is usually the most effective step. For Siemens systems, see Flair Facilities’ Siemens BMS engineer service, and for a real example of tracing linked heating, hot water and controls faults, read the hotel heating and BMS case study.

How it works

Our process

  1. Step 1

    Describe the fault

    Tell us what you are seeing, which plant or zones are affected and any alarm messages.

  2. Step 2

    Review the data

    Where available, alarms and trend logs are reviewed, sometimes remotely, before attending.

  3. Step 3

    Diagnose on site

    Commanded versus actual behaviour is tested at the device, controller and network.

  4. Step 4

    Repair and report

    The fault is put right, tested and documented, with any further actions recommended.

flairfacilities.co.uk

More on bms repair & fault finding from Flair Facilities

BMS repair & fault finding: questions

Can you repair a BMS installed by another contractor?

Yes, provided the system uses standard protocols and the controller programmes can be accessed. If documentation is missing, we review the system first so the repair does not create new problems.

Can BMS faults be diagnosed remotely?

Often. Where secure remote access is available, alarms, trend logs and controller states can be reviewed before an engineer attends, and some faults can be resolved remotely. Physical faults such as a seized actuator still need a site visit.

What information should we have ready?

The affected plant or zones, when the problem started, alarm messages, any recent works or changes, and, if possible, BMS trend data. Our guide on preparing BMS data explains what helps most.

Is it the BMS or the plant?

That is the first question fault finding answers. If the BMS is commanding the right action and the plant does not respond, the fault is usually in the device or plant. If the BMS is commanding the wrong action, the fault is in sensors, logic or settings.

What if the boiler or AHU itself has failed?

Flair Facilities Ltd also works on commercial boilers, HVAC and plant rooms, so mechanical faults found during BMS diagnosis can be dealt with by the same company.