02 · Commercial HVAC

AHU Troubleshooting: Diagnosing Air Handling Unit Faults

  • By Flair Facilities Ltd engineering team
  • Published
  • Updated
  • Read 7 min
Quick answer

Most air handling unit (AHU) problems fall into three groups: airflow faults (blocked filters, slipping belts, failed fans or stuck dampers), temperature faults (heating or cooling coil valves, low water temperatures or failed sensors) and safety trips (frost protection, fire alarm interlocks or fan proving). Checking BMS alarms, filter pressure drops and supply air temperature against setpoint usually narrows the cause before an engineer opens the unit.

How does an air handling unit work?

An AHU conditions and moves air for a building or zone. Air passes through a sequence of sections, each of which can fail independently:

SectionFunctionTypical faults
Inlet and dampersAdmit fresh air, mix with return airSeized dampers, failed actuators, blocked louvres
FiltersRemove particlesOverloaded filters, bypass around frames
Heat recoveryTransfer heat between extract and supplyWheel drive failure, plate exchanger fouling, frost
Heating coilWarm air using LTHW or electric heaterValve not opening, air-locked coil, low water temperature
Cooling coilCool and dehumidify using chilled water or DXValve faults, blocked drains, fouled fins
FanMove air through the systemBelt slip, bearing wear, motor or drive failure
Controls and sensorsRegulate temperature, pressure and airflowSensor drift, poor tuning, interlock trips

Common symptoms

  • Rooms stuffy or warm despite the AHU “running”
  • Supply air temperature drifting from setpoint
  • AHU tripping on frost protection in cold weather
  • Filter alarms appearing soon after changes
  • Squealing, rumbling or vibration from the fan section
  • Water leaking from the unit or under it
  • High energy use or plant running out of hours

Potential causes by symptom

Low airflow

Blocked filters, slipping or broken drive belts, a failing fan motor or variable speed drive, closed dampers or fire dampers, and blocked coils. If fan current or speed is trended on the BMS, a sudden drop points to the drive; a gradual decline points to filters or fouling.

Supply air too cold or too warm

Check whether the heating or cooling valve is responding to BMS demand. A valve commanded 100% open with no temperature rise suggests a seized actuator, an air-locked coil or low LTHW or chilled water temperatures. A drifting sensor can also give false readings, as explained in BMS temperature sensor faults.

Frost trips

Usually triggered on cold mornings at start-up. Causes include heating valves that open too slowly, low water temperature at the coil, fresh air dampers opening before the coil is warm, frozen heat recovery, or a faulty frost sensor. Repeated frost trips must not be solved by lowering or bypassing the frost setpoint.

Noise and vibration

Belt squeal, worn bearings, fan imbalance from dirt build-up, loose panels or failed anti-vibration mounts.

Water leaks

Blocked condensate drains or traps under the cooling coil, failed drain pans, or coil or valve leaks.

Safety: AHUs contain rotating fans that may start automatically under BMS control, electrical supplies and, in some units, electric heaters and refrigerant. Never open fan section doors without isolating and locking off the unit. Do not reset fire alarm interlocks or frost trips repeatedly without understanding the cause.

Diagnostic considerations

  1. Read alarms and status in the BMS: fan run status, proving, filter differential, frost status and supply temperature.
  2. Trend the key points: supply temperature, setpoint, valve positions, damper positions and fan speed over at least 24 hours.
  3. Compare commanded versus actual: a valve or damper commanded but not moving is a field device fault.
  4. Check water-side supply: LTHW and chilled water temperatures at plant.
  5. Correlate with weather and time: frost trips and comfort complaints often cluster around start-up.

When should you involve a qualified engineer?

Call an HVAC engineer for fan, motor and drive faults, refrigerant systems, electric heater faults, repeated frost or fire interlock trips, water leaks inside the unit, and any work requiring panels to be opened. Controls engineers should handle sensor replacement and control logic changes.

Practical recommendations for facilities managers

  • Ensure filter differential pressure is monitored and alarmed
  • Trend supply temperature, valve positions and fan speed on every AHU
  • Check time schedules match occupancy
  • Schedule coil cleaning and drain checks before the cooling season
  • Keep a record of frost trips with times and outside temperatures
  • Verify heat recovery is operating and not bypassed unintentionally

For the wider context, see our Commercial HVAC guide.

flairfacilities.co.uk

More BMS expertise from Flair Facilities

Frequently asked questions

What does an AHU frost trip mean?

A frost thermostat or sensor downstream of the heating coil has detected air close to freezing. The AHU shuts down to protect the coils from bursting. Common causes are a failed heating valve, low LTHW temperature, a damper fault letting in too much cold air, or a failed frost sensor.

Why is the AHU running but rooms are not ventilated?

Possible causes include closed or failed dampers, a fan running at reduced speed, slipping drive belts, heavily loaded filters, or ductwork dampers closed downstream. Measured airflow or fan speed in the BMS helps confirm it.

How do I know when AHU filters need changing?

Use the differential pressure across the filter bank. Filter manufacturers give a recommended final pressure drop. Many BMS installations alarm when this is reached.

Can a faulty AHU affect energy bills?

Significantly. Failed heat recovery, plant running out of hours, simultaneous heating and cooling and excessive fan speeds all increase energy use without improving comfort.

UK technical references

Primary sources and industry guidance relevant to this topic. Always check you are working to the current edition.

  1. Ventilation in the workplace — Health and Safety Executive
  2. Workplace (Health, Safety and Welfare) Regulations 1992 — legislation.gov.uk
  3. Approved Document F: Ventilation — GOV.UK
  4. SFG20 maintenance standard — BESA / SFG20

This guide is general technical information for commercial property teams in the UK. It does not replace a site-specific assessment. Gas work must be carried out by a Gas Safe registered engineer, and work on electrical, pressurised or combustion equipment by competent, appropriately qualified people.