A pressurisation unit keeps a sealed heating or chilled water system topped up to its design pressure. Faults usually show as low or high pressure alarms, the unit running too often, or pumps that run without raising pressure. The cause is often not the unit itself: leaks, failed expansion vessels, an empty break tank or wrong settings are common. Frequent top-ups should always be investigated because they introduce oxygen and accelerate corrosion.
What does a pressurisation unit do?
A pressurisation unit is a packaged set, usually a small break tank, one or two pumps and a controller with a pressure sensor, connected to a sealed system. When pressure falls below the cut-in point, a pump starts and adds water until pressure reaches the cut-out point. Units typically include low and high pressure alarms that can stop boilers or signal the BMS.
The pressurisation unit does not work alone. It relies on correctly charged expansion vessels to absorb thermal expansion. The combination determines how stable system pressure is between cold and hot conditions.
Common symptoms
- Low pressure alarm on the unit, boilers or BMS
- High pressure alarm or relief valves discharging
- Pump running frequently or continuously
- Pump running but pressure not rising
- Break tank overflowing or running dry
- Noisy pump operation, or the pump short-cycling
Potential causes
| Symptom | Likely causes |
|---|---|
| Frequent top-ups | System leak, relief valve discharging, automatic air vent leaking, failed expansion vessel |
| Pressure not rising | Empty break tank, failed float valve, air-locked or worn pump, outlet valve closed |
| Low pressure alarm with pump idle | Unit in alarm lockout, failed sensor, power or control fault |
| High pressure | Failed vessel, incorrect cut-out setting, faulty sensor, solenoid passing water |
| Pump short-cycling | Waterlogged vessel, very small cut-in/cut-out differential, faulty non-return valve |
| Break tank overflowing | Float valve not closing |
The expansion vessel connection
When an expansion vessel loses its gas charge, system pressure rises sharply as the water heats and falls sharply as it cools. The pressurisation unit then cycles more often to compensate, and relief valves may lift on the high side. This is one of the most common causes of “pressurisation unit faults” that are not faults in the unit at all.
Diagnostic considerations
- Record cold and hot pressures for several days. A large swing suggests a vessel problem.
- Check the break tank level and whether the float valve is working.
- Check pump starts or run hours if the controller records them.
- Look for discharge at relief valve tundishes and drains.
- Verify settings against the commissioning record: cut-in, cut-out, alarms and fill pressure.
- Have the expansion vessel pre-charge checked by an engineer with the vessel isolated and drained on the water side.
Safety: Expansion vessels and pressurisation units are pressurised. Never attempt to check vessel pre-charge on a live system, remove vessel caps or adjust pressure settings unless you are competent and the equipment is isolated. Relief valve discharge can be scalding on heating systems.
When should you involve an engineer?
Call an engineer when alarms recur, when the unit is topping up more than usual, when relief valves discharge, when vessels need checking or recharging, or when pumps are worn or noisy. If top-ups suggest a leak, a leak investigation is the next step. See why heating systems lose pressure.
Practical recommendations for facilities managers
- Record the design fill pressure, cut-in, cut-out and alarm settings in the plant room log
- Log pressure readings and pump starts weekly
- Include expansion vessel pre-charge checks in annual PPM
- Inspect break tank, float valve and overflow during plant room walk-rounds
- Investigate any increase in top-up frequency
- Review water treatment results after periods of heavy top-up
For the wider system, see Plant Room Engineering and Water Pressure and Pumps.
Frequently asked questions
How often should a pressurisation unit top up a system?
In a healthy, leak-free system, top-ups should be infrequent. A sudden increase in pump starts or water consumption is a sign of a leak, relief valve discharge or vessel failure.
What is expansion vessel pre-charge?
The gas pressure behind the vessel membrane, set at a value related to the system's cold fill pressure. If it falls, the vessel fills with water and can no longer absorb expansion. Pre-charge must be checked with the vessel isolated and drained on the water side.
Why is the pressurisation unit pump running but pressure is not rising?
Possible causes include an empty or low break tank, air-locked pump, worn pump, a closed outlet valve, or water leaving the system as fast as it is added.
Can a pressurisation unit cause high pressure?
Yes, if a pressure switch or transducer fails, if the cut-out setting is wrong, or if a solenoid valve lets water through. High pressure can lift relief valves and should be investigated promptly.
UK technical references
Primary sources and industry guidance relevant to this topic. Always check you are working to the current edition.
- Pressure systems guidance — Health and Safety Executive
- Water Supply (Water Fittings) Regulations 1999 — legislation.gov.uk
- BSRIA guidance on water treatment — BSRIA
- SFG20 maintenance standard — BESA / SFG20
This guide is general technical information for commercial property teams in the UK. It does not replace a site-specific assessment. Gas work must be carried out by a Gas Safe registered engineer, and work on electrical, pressurised or combustion equipment by competent, appropriately qualified people.